ASHRAE – Chilled Water Pipe Sizing Chart
ASHRAE – Chilled Water Pipe Sizing Chart
Download : Chilled Water Pipe Sizing Chart
ASHRAE CHAPTER 33 – A variety of upper limits of water velocity and/or pressure drop in piping and piping systems is used. One recommendation places a velocity limit of 4 fps for 2 in. pipe and smaller, and a pressure drop limit of 4 ft of water/100 ft for piping over 2 in.
4 Comments
i request you to all hvac equation and mep project check list
Thank you Rizwan.
For my thesis, I consulted a lot of information, read your article made me feel a lot, benefited me a lot from it, thank you for your help. Thanks!
Very glad that it helped you a lot… kudos.